For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown in the Maximum Allowable Ampacities table by the appropriate factor shown below.
60°C (140°F) |
75°C (167°F) |
90°C (194°F) |
60°C (140°F) |
75°C (167°F) |
90°C (194°F) |
||
---|---|---|---|---|---|---|---|
AMBIENT TEMP | TYPES TW, UF |
TYPES RHW, THW, THWN |
TYPES TBS, SA, SIS |
TYPES TW, UF |
TYPES RHW, THW, THWN |
TYPES TBS, SA, SIS |
AMBIENT TEMP |
°C | COPPER | ALUMINUM | °F | ||||
21-25 | 1.08 | 1.05 | 1.04 | 1.08 | 1.05 | 1.04 | 70-77 |
26-30 | 1 | 1 | 1 | 1 | 1 | 1 | 78-86 |
31-35 | 0.91 | 0.94 | 0.96 | 0.91 | 0.94 | 0.96 | 87-95 |
36-40 | 0.82 | 0.88 | 0.91 | 0.82 | 0.88 | 0.91 | 96-104 |
41-45 | 0.71 | 0.82 | 0.87 | 0.71 | 0.82 | 0.87 | 105-113 |
46-50 | 0.58 | 0.75 | 0.82 | 0.58 | 0.75 | 0.82 | 114-122 |
51-55 | 0.41 | 0.67 | 0.76 | 0.41 | 0.67 | 0.76 | 123-131 |
56-60 | – | 0.58 | 0.71 | – | 0.58 | 0.71 | 132-140 |
61-70 | – | 0.33 | 0.58 | – | 0.33 | 0.58 | 141-158 |
71-80 | – | – | 0.41 | – | – | 0.41 | 159-176 |
For more than three current-carrying conductors in a raceway or cable, multiply the allowable ampacities shown in the Maximum Allowable Ampacities table by the percentages shown below.
Number of Current-Carrying Conductors | Percent of Values in Tables 310.15(B)(16) through 310.15(B)(19) as Adjusted for Ambient Temperature if Necessary |
---|---|
4-6 | 80 |
7-9 | 70 |
10-20 | 50 |
21-30 | 45 |
31-40 | 40 |
41+ | 35 |