The ampacity chart below shows allowable ampacities of insulated conductors rated up to and including 2000 Volts, 60°C through 90°C (140°F through 194°F), not more than three current-carrying conductors in raceway, cable, or earth (directly buried), based on ambient air temperature of 40°C (104°F).
SIZE | 150°C (302°F) |
200°C (392°F) |
250°C (482°F) |
250°C (482°F) |
250°C (482°F) |
450°C (842°F) |
450°C (842°F) |
---|---|---|---|---|---|---|---|
AWG or kcmil |
TINNED COPPER | TINNED COPPER NPC 2%-10% |
NPC 2%-10% | "A" NICKEL | NPI | NPC 27% | "A" NICKEL |
14 | 34 | 36 | 39 | 18 | 16 | 45 | 21 |
12 | 43 | 45 | 54 | 25 | 22 | 56 | 26 |
10 | 55 | 60 | 73 | 34 | 30 | 75 | 35 |
8 | 76 | 83 | 93 | 43 | 39 | 104 | 49 |
6 | 96 | 110 | 117 | 55 | 49 | 138 | 65 |
4 | 120 | 125 | 148 | 69 | 62 | 162 | 76 |
3 | 143 | 152 | 166 | 78 | 69 | 182 | 85 |
2 | 160 | 171 | 191 | 90 | 80 | 210 | 99 |
1 | 186 | 197 | 215 | 101 | 90 | 236 | 110 |
1/0 | 215 | 229 | 244 | 114 | 102 | 268 | 126 |
2/0 | 251 | 260 | 273 | 128 | 114 | 300 | 141 |
3/0 | 288 | 297 | 308 | 144 | 129 | 338 | 159 |
4/0 | 332 | 346 | 361 | 169 | 151 | 397 | 186 |
250 | 365 | 385 | 398 | 187 | 167 | - | - |
300 | 414 | 436 | 452 | 212 | 190 | - | - |
350 | 461 | 486 | 503 | 236 | 211 | - | - |
400 | 495 | 522 | 540 | 254 | 226 | - | - |
500 | 563 | 593 | 613 | 288 | 257 | - | - |
Note: View additional wire size charts from the list below.
For ambient temperatures other than 40°C, Correction Factors must be taken into consideration.