The ampacity chart below shows the allowable ampacities of single-insulated electrical wire rated up to and including 2000 Volts in free air, based on Ambient Air Temperature of 40°C (104°F).

Wire Size Chart:
Allowable Ampacities of Conductors in Free Air

Source: NFPA 70, National Electrical Code, Table 310.15(B)(19)
SIZE 150°C
(302°F)
200°C
(392°F)
250°C
(482°F)
150°C
(482°F)
AWG
or
kcmil
TINNED COPPER TINNED COPPER
NPC 2%-10%
NPC 2%-10% ALUMINUM
14 46 54 59 -
12 60 68 78 47
10 80 90 107 63
8 106 124 142 83
6 155 165 205 112
4 190 220 278 148
3 214 252 327 170
2 255 293 381 198
1 293 344 440 228
1/0 339 399 532 263
2/0 390 467 591 305
3/0 451 546 708 351
4/0 529 629 830 411

Note: View additional wire size charts from the list below.


For ambient temperatures other than 40°C, Correction Factors must be taken into consideration.